Câble de puissance PP-601

TEMPSENS · PP-601

Power Cable (PP-601)

Power Cable (PP-601) — Construction: PVC — inner PVC — G.I. round wire or flat strip — outer PVC sheath, rated to 90 °C.

Request a quote

Category: Industrial sensors · Power cables & lead wires

Specifications by model

Cable ordering codeCross-section area (mm²)Wire typeInsulation thickness (nom.)Inner sheath thickness (min.)G.I. armour — round wire (mm)G.I. armour — flat strip (mm)Sheath thickness (min.)Nominal cable diameter (mm)Max. conductor resistance @ 20 °C (Cu)Cable weight (approx.), kg/km
PP6011.5Solid / stranded0.80.31.4-1.2413.312.1480
PP6022.5Solid / stranded0.90.31.4-1.2414.77.41590
PP6034.0Solid / stranded1.00.31.4-1.2416.34.61749
PP6046.0Solid / stranded1.00.31.4-1.2417.63.08878
PP60510.0Stranded (class 2)1.00.3-0.81.418.41.831050
PP60616.0Stranded (class 2)1.00.3-0.81.420.81.151275
PP60725.0Stranded (class 2)1.20.3-0.81.424.50.7271748
PP60835.0Stranded (class 2)1.20.3-0.81.4270.5242350
PP60950.0Stranded (class 2)1.40.3-0.81.7231.80.3873040
PP61070.0Stranded (class 2)1.40.3-0.81.5635.40.2683930

Full description

Power Cable (PP-601). Features: Conductor: solid or multistrand, bare copper or tinned plated copper. Core insulation: PVC (Type A), HR PVC (Type C) or PVC (Type D). Construction: twisted. Inner sheath: PVC, HR PVC, FR PVC, FRLS PVC or LSZH. Armouring: galvanised round wire or flat strip as per IS 3975. Outer jacket: PVC, HR PVC, FR PVC, FRLS PVC or LSZH. Operating temperature: 90 °C. Part Code: PP-601 Conductor : Solid, Multistrand, Bare Copper, Tinned Plated Copper Core Insulation : PVC(Type A), HR PVC(Type C), PVC (Type D) No. of Core : 4 Construction : Twisted Inner Sheath : PVC, HR PVC, FR PVC, FRLS PVC, LSZH Armouring : Galvanised round wire / flat strip as per IS 3975 Outer Jacket : PVC, HR PVC, FR PVC, FRLS PVC, LSZH Operating Temp. : 90°C